Overhead Transmission Line Sag Monitoring Using a Chirped-Pulse Phase-Sensitive OTDR

Published in : IEEE Sensors Journal (Volume: 24, Issue: 2, January 2024)
Authors : Canudo Jorge, Subias Jesus, Sevillano Pascual, Preciado-Garbayo Javier, Kwik Sacha, Iranzo Andrea
DOI : https://doi.org/10.1109/JSEN.2023.3340296
Summary Contributed by:  Jorge Canudo (Author)

The conductor's dip, or the curve of overhead power lines between their towers, known as sag, determines how much electricity the line can safely carry. Heating causes the lines to expand and sag, increasing the risk of an electrical discharge. Continuous monitoring is challenging; hence, for safety, operators set the line's capacity lower than it is capable of.

Measuring sag directly is difficult. Cameras, GPS receivers, laser rangefinders, tension sensors, and inspection robots work, but each can monitor only a single span. A line with 100 spans would need 100 instruments, each installed on a live high-voltage structure and requiring power, communication, and maintenance.

Modern overhead lines are equipped with an optical ground wire that serves as a lightning shield and carries optical fibers. A spare dark fiber in this setup can be used as a distributed sensor. Researchers connected a chirped-pulse distributed fiber-optic sensor to one end of the optical ground wire inside a substation, which sent laser pulses down the fiber and detected the faint light scattered back, enabling it to measure the strain experienced by the fiber along the 31.8 km line, taking one measurement every 10 meters and achieving 250 measurements per second. A single unit of this technology can cover approximately 40 km of installation.

What the fiber registers is wind striking the cables. As air flows past a conductor, it creates vortices that make the cable swing. Each span vibrates like a string clamped at both ends. The pitch of the vibrating string depends on the span length and the cable tension, which directly influence its sag. Therefore, the vibration frequency provides a precise, calibration-free measurement of how low the cable hangs. The stronger winds may increase the loudness of the vibration, but they do not change the pitch.

To recover the fundamental frequency, the strain readings from the interrogator were transformed into the frequency domain. Each span appears as a distinct set of frequency lines, which indicates the starting and ending points of each span along the route. A tracking algorithm monitors these lines over time, distinguishing the cable's true harmonics from vibrations transmitted by the towers, and extracting the fundamental frequency, from which the sag can be calculated using a simple formula.

During testing on a 220-kV line, the frequencies showed a clear 24-hour cycle, rising and falling in correlation with the air temperature. This behavior was expected, as the metal expands during the day as temperatures rise and contracts at night as temperatures drop. For one 421-meter span, the computed sag varied by approximately 0.6 m in a day. When compared to measurements taken with a laser telemeter aimed at the conductor from the ground, the fiber-based estimate of that change agreed to within roughly 8 centimeters.

Though the analysis is not yet fully automatic and strong gusts can briefly drown the signal, the principle remains that a transmission line can be designed to report its own sag, span by span, using fiber already in use, with just a single device.